Description
Application Scenarios
On a mid-life overhaul of a single-shaft gas turbine running a Mark V Speedtronic control panel, the controls technician opens the core cabinet during the annual shutdown and performs the standard TCPD verification: with the 125 V DC battery feed live and the board’s 8 toggle switches in their commissioned positions, all 36 green OK LEDs should be illuminated. During one such inspection, LED FU14 was found dark while its neighboring circuits stayed lit — the classic signature of a single blown branch fuse rather than a board-level power loss. Because the DS200TCPDG1BEC isolates each module feed on its own fuse and LED, the technician pulled the FU14 canister (black plastic housing, twist-top), confirmed the fuse element had opened, replaced it with the documented rating from the Mark V system manual, and watched the LED re-light immediately — a five-minute intervention that avoided losing a single control module, let alone the panel.worldofcontrols.com+1
That workflow — per-circuit fuse protection and LED-indicated status across a rack of turbine control modules fed from a single 125 V DC battery source — is exactly the design problem the DS200TCPDG1BEC was built to solve: in gas turbine protection duty (overspeed, vibration, flame detection), steam turbine governor duty, combined-cycle multi-rack installations, and black-start / emergency-power turbine services where the control electronics must remain live even when the AC auxiliary supply is unavailable.auto2mation.com
Parameter
| Main Parameters | Value / Description |
|---|---|
| Product Model | DS200TCPDG1BEC |
| Manufacturer | General Electric (GE) |
| Product Category | Power Distribution Board (TCPD — Turbine Control Power Distribution) |
| Product Series | Mark V Speedtronic turbine control system |
| Input Voltage | 125 V DC nominal (plant battery system) |
| Distribution | Multiple branch circuits for logic and field power |
| Fused Outputs | 36 individually fused circuits |
| Status Indicators | 36 OK LEDs (one per fused circuit); 2 additional red board-level fault LEDs on the 1B variant |
| Toggle Switches | 8 (manual isolation of specific power circuits) |
| Signal Wire Terminals | 4 |
| Board Connector | 1 × 10-pin connector |
| Protection Elements | Integrated fuses and MOVs (metal-oxide varistors) for transient suppression |
| Powered Modules | TCPS, TCEA, TCTG, DTBC, DTBD, CTBA and other Mark V core cards |
| Fuse Identification | FU-prefix numbering (FU1, FU2, … FU36) |
| PCB Construction | 94V-0 flammability rating; normal protective coating |
| Operating Temperature | 0 °C to 60 °C (internal cabinet ambient) |
| Test Points | On-board voltage verification points |
| Weight | ~0.62 kg (1BEC variant; heavier frame up to ~10.5 kg reported on the 2BEC variant) |
| Revision Suffix | B = 1st functional revision; E = 2nd functional revision; C = artwork revision |
| Country of Origin | USA |
| Configuration Compatibility | Simplex and TMR (Triple Modular Redundant) Mark V systems; R / S / T core positions |
| Lifecycle Status | Discontinued; supported through new surplus, refurbished stock, and repair services |